Ventilation fans
A purpose-built exhaust fan for BESS enclosures, providing 1,200 CFM airflow to vent leaked combustible gases and reduce gas accumulation.
Technical Specifications
Item
Specification
Model
KS-Blast-P1200 Series
Maximum Airflow
1,200 CFM (+10%)
Dimensions
450 × 400 × 50 mm
Mounting Cutout
395 × 340 mm
Power Supply
Exhaust: 230 V AC (±10%); intake: 24 V (±10%)
Noise Level
≤85 dB
Operating Temperature
−40 to +70°C
Operating Humidity
5–95% RH
Storage Temperature
−40 to +70°C
Storage Humidity
≤95% RH
Protection Rating
IP66 (after installation)
Corrosion Resistance
C5
Explosion Protection / Fan
Ex ec IIC T4 Gc
Explosion Protection / Actuator
Ex db IIC T4 Gb
Operating Pressure
55–110 kPa
Operating Altitude
≤5,000 m
Seal Material
EPDM
Lifetime
Fan ≥50,000 h; actuator ≥6,000 cycles
Housing / Finish
Metal / RAL 7035
Communication
RS485